Before you start

  • You need Inventory Management.
  • The project's system type is Room splits. The sizing banner reads "Units are sized per space".
  • Your items include room split units with the AC Systems category and an equipment type. See "No equipment found" or "Type not set".

Steps

  1. Open AC Unit Recommendations for the project. See Open AC Unit Recommendations for a project.

  2. Find the Units per space table on the Choose AC Systems card: "Choose a unit for each space. Recommended is the smallest size that covers the load."

    Step 2. The Units per space table with Recommended, Chosen unit and Qty.
    Step 2. The Units per space table with Recommended, Chosen unit and Qty.
  3. On each space's row, select Use to take the Recommended unit, or pick one in Chosen unit.

  4. Set Qty.

  5. If a row shows "from heat load" with "Proposed on heat load: [text]", select Confirm to keep the unit proposed on the heat load results.

  6. To give a space a second unit, select Add another unit.

  7. Read each row's verdict and the totals line.

  8. Save the selection. See Save your equipment selection.

Result

Every space has its chosen unit and quantity, with a verdict per row. Nothing is saved until Save selection.

If something is different

  • "No [types] in your items. Set equipment types on the Items page.": see "No equipment found" or "Type not set".
  • "Unit not in the current list": a unit saved earlier is no longer offered, for example its equipment type changed.
  • "Not assigned to a room": units saved without a space are listed below the table, with "was [space]" when they had one. Choose a space in Assign, or select Remove.
  • A row's verdict is short or oversized: see The verdict says short or oversized.
  • "To be ordered": the unit has no stock. You can still choose it.
  • A space shows its load in kW: it needs heating only.
  • "Units are chosen per space in the table below.": room split projects have no Get Recommendations.