The form is titled "EN 12831-1 Design Heat Load: Heating Load", with the space's status badge. The screen says "Per EN 12831-1:2017." Every value is in SI.

Space & design temperature

FieldWhat to enter
Space nameFor example "Apartment 3B".
External design temp θ_e (°C)Typed by hand. "By department from the national annex: never a weather station (Paris −7, Nice −2, Grenoble −15 °C)."
θ_e source noteRequired. Where the temperature comes from, for example "NF EN 12831 annex, dépt. 75".
Ground b-factorFor example 0.4.
SimultaneityFor example 1.0.

Each room

Each room has its own card, "Room [number]". Add room adds another.

FieldDefault or options
NameRoom 1
TypeDefault living
Floor area (m²)
Height (m)2.5
n_min override (1/h)Blank uses the room type's default.
Mechanical (m³/h)
ReheatTick box.
f_RH (W/m²)For example 11.

Each envelope element

Under Envelope elements, Element adds a row.

FieldOptions
Kindwall, roof, floor, window, door, partition
Area m²
U W/m²K
Adjacencyexterior, ground, unheated, heated other
Adj °CShown when the adjacency is heated other.

Results

"Results · Building heating load": the total in kW, then one row per room with the columns Room, θ_int, Transmission (W), Ventilation (W), Reheat (W) and Total (W). A field the server refuses shows as "[field]: [message]".